online three phase modular UPS 20KVA to 400KVA, DSP control

FOB Price: Get Latest Price
Model:EA66200 200KVA
Certification:CE
Capable:UL
Minimum Order:10
Brand Name:EAST
Brief Description:Ideal Application: IDC room, IT room, ISP server center, telecom, finance, securities, traffic, tax, medical system.

Doreen Zhang

  • Product Details

Basic Specification

Output Voltage380V /400V / 415VAac
Weight280kg
ProtectionOvercurrent
ApplicationComputer, Instrumentation, Medical, Military, Networking, Other, Security / Monitoring / Alarm, Telecommunications
PhaseThree Phase
TypeOn-line

Detail Description

 Features

 

  • High frequency online double-conversion with DSP control
  • Hot swappable operation for all modules
  • Inbuilt integrated PDU system, easy installation and economic initial investment
  • Wide input voltage range, 50Hz / 60Hz auto sensing frequency
  • Support two modes of frequency conversion: 50Hz input/60Hz output and 60Hz input / 50Hz output
  • Input power factor>0.99, input THDi≤3%, output THDV≤3%
  • Advanced “N+X” wireless parallel and redundancy technology easily set up different numbers of redundancy UPS module via LCD
  • Inbuilt battery module available, 40×12V/9AH for each module
  • Share battery pack in parallel operation, saving user’s battery cost
  • System capacity up to 400KVA/400KW constructed by each module 20KVA / 20KW, single charger module be equipped with 30 A charging current,4 modules be configured maximally
  • Flexible charger parameter and battery configuration setting, selectable battery number: 32 pcs / 34 pcs / 36pcs / 38 pcs / 40 pcs
  • Advanced intelligent battery management technique, prolong the working life of battery effectively
  • Support battery cold start and mains auto restart
  • Completely isolation design between fragile components and air flue, improving the system reliability greatly
  • Fragile components been replaced as module easily at low maintenance cost
  • Front door operation, available for top and bottom terminal connection
  • Perfect protection for hardware and software (C class lighting protection, circuit breaker, fuse, software and hardware protection), robust self detection, abundant event log for future check
  • 5.7 inches LCD touch screen, friendly human & machine interface
  • Standard emergency power off (EPO)
  • Standard RS232/USB/RS485/dry contacts communication port
  • Optional SNMP communication port
  • Optional battery temperature compensation

 

Technical data

MODEL

EA6680

EA66160

EA66200

EA66400

Capacity

80 KVA / 80 KW

160 KVA / 160 KW

200 KVA / 200 KW

400 KVA / 400 KW

Numbers of parallel module

1~4

1~8

1~10

1~20

Numbers of redundancy module

0~3

0~7

0~9

0~19

UPS power module

20 KVA / 20 KW

INPUT


Rated voltage

380 V / 400 V / 415 Vac

Voltage range

204~520 Vac (load ≤ 50%);
242~520 Vac (50% < load ≤ 70%);
277V~520 Vac (70% < load ≤ 100%)

Rated frequency

50 / 60 Hz (auto-sense)

Frequency range

40 ~ 70 Hz

Power factor

≥ 0.99

Total harmonic distortion (THDI)

≤ 3%

Bypass voltage range

Rated output voltage - 40% ~ rated output voltage + 20% (settable via LCD)

OUTPUT


Voltage

380 V / 400 V / 415 Vac

Voltage regulation

± 1%

Frequency

Synchronized with utility in mains mode;
50 / 60 Hz ± 0.1% in battery mode

Power factor

1.0

Waveform

Pure sine wave

Crest factor

3:1

Total harmonic distortion (THDV)

≤ 1% (linear load); ≤ 3% (non-linear load)

Transfer time

0ms

Inverter overload capability

110% ~130%: transfer to bypass in 10 mins;
130% ~ 150%: transfer to bypass in 1 min;
> 150%: transfer to bypass in 0.5 s

Bypass overload capability

≤ 150%: long time running
> 150%: power off in 10 s

BATTERIES


DC voltage

± 240 V (options: ±192 V / ± 204 V / ± 216 V / ± 228 V)

Inbuilt battery of standard model

40×12 V / 9 Ah for each module

 Charging current

1 ~ 30 A / 60 A (settable via LCD)

1 ~ 60 A / 120 A (settable via LCD)

SYSTEM


Efficiency

≥ 94%

Display panel

5.7 Inches LCD touch screen

Alarm

Battery mode, low battery, fans fault etc.

EMI

EN62040-2

EMS

IEC61000-4-2 (ESD)

IEC61000-4-3 (RS)

IEC61000-4-4 (EFT)

IEC61000-4-5 (Surge)

COMMUNICAITONS


RS232 / RS485 / USB / dry contacts (standard)

Supports Windows® 98 / 2000 / 2003 / XP / Vista / 2008 / 7 / 8 / 10

SNMP (option)

Power management from SNMP manager and web browser

OTHERS


Humidity

0~95% RH @ 0~40℃ (non-condensing)

Noise level

≤ 60 dB

Module dimensions (W×D×H)  (mm)

482×590×131

Module weight

28 kg / power module, 27 kg / charger module, 7 kg / monitoring module

UPS dimensions (W×D×H) (mm)

600×1000×1600

600×1000×2000

1200×1000×2000

UPS packaged dimensions (W×D×H) (mm)

700×1070×1760

700×1070×2160

700×1070×2160(×2)

UPS Net/Gross weight (kg)
Without inbuilt battery and power module

225 / 245

290 / 310

280 / 300

560 / 600

Input / output / bypass breaker

Yes

Yes

No

No

Additional Information

Payment TermsL/C, T/T, D/A, D/P, Credit Card, Western Union, Money Order, Paypal, Others
Minimum Order10
Lead Time / Delivery Time20 Day(s)
Sample AvailableYES Ask For Sample
Delivery DetailsSample order, 7 days after pyament receiveRegular order, 20 days after order confirmed.
FOB PortShenzhen,
Loading InfoFOB Shenzhen base on containerEXW base on LCL
Packing Info1PCS/CTN
Target Market(s)North America, Oceania, Southeast Asia, Eastern Europe, Africa(except Middle East), Hong Kong/ Macao/ Taiwan, Latin America, Japan & Korea, Middle East & South Asia, Mainland China, Western & Southern Europe, Northern Europe, Central & Southern Asia, Middle East

Send your message to this manufacturer


3000
SearchPost Buying Lead